Transmission Service Request Studies
​To request a copy of the study, please email the following information to studyrequest@bpa.gov; name, title, company, mailing address, and telephone number. BPA Transmission Services will then contact you with non-disclosure requirements. Upon approval, a copy of the study will be provided.  
4/27/2011​
BPA-TS TPP-2011-044 2010 NOS Cluster Study 
In June 2010, BPA-TS conducted a Network Open Season. Customers executed Precedent Transmission Service Agreements (PTSA''s) requesting a total of 3759 MW of long-term firm transmission service. The Cluster Study assessed the impacts of the requested service and determined the system reinforcements necessary to provide the requested service. This report summarizes the results of the technical studies, the estimated costs, and the earliest in-service dates. The Cluster Study concluded that a) there was sufficient ATC for 53 MW with no further requirements beyond those required for interconnection, b) upon completion of the infrastructure additions that resulted from the 2008 NOS there would be sufficient ATC for 1522 MW of the requests, and c) 2184 MW of the requests require both the infrastructure additions that resulted from the 2008 NOS and additional facilities identified in the Cluster Study. 4/27/11​
4/22/2010​ BPA-TS TPP-2010-016 2009 NOS Cluster Study
In June, 2009, BPA-TS conducted a Network Open Season. Customers executed Precedent Transmission Service Agreements (PTSA''s) requesting a total of 1553 MW of transmission service. BPA-TS had sufficient Available Transfer Capability (ATC) to grant 293 MW of those requests across the existing transmission system. The study concluded that upon completion of the infrastructure additions that resulted from the 2008 NOS, there was sufficient ATC for 1121 MW of those requests. The study also concluded that 139 MW of those requests required additional facilities. The Study assessed the impacts of the requested service and determined the system reinforcements necessary to provide the requested service. This report summarizes the results of the technical studies, the estimated costs, and the earliest in-service dates. 4/23/10. ​
4/21/2010
BPA-TS Cluster Study for 2009 Network Open Season
In June, 2009, BPA-TS conducted a Network Open Season. Customers executed Precedent Transmission Service Agreements (PTSA''s) requesting a total of 1553 MW of transmission service. BPA-TS had sufficient Available Transfer Capability (ATC) to grant 293 MW of those requests across the existing transmission system. The study concluded that upon completion of the infrastructure additions that resulted from the 2008 NOS, there was sufficient ATC for 1121 MW of those requests. The study also concluded that 139 MW of those requests required additional facilities. The Study assessed the impacts of the requested service and determined the system reinforcements necessary to provide the requested service. This report summarizes the results of the technical studies, the estimated costs, and the earliest in-service dates. 04/23/2010
3/25/2009 ​
BPA-TS TPP-2008-092 2008 NOS Cluster Study
BPA-TS completed a Cluster Study in response to the 2008 Network Open Season (NOS). In April, 2008, BPA-TS conducted a Network Open Season. Customers executed Precedent Transmission Service Agreements (PTSA''s) requesting a total of 6,410 MW of transmission service. BPA-TS had sufficient Available Transfer Capability (ATC) to grant 1,782 MW of those requests. In order to grant the remaining 4,628 MW of transmission service, BPA-TS conducted a Cluster Study (Study). The Study identifies how the requests were grouped into study areas and the methodology used to study impact of the requests. The Study assessed the impacts of the requested service and determined the system reinforcements necessary to grant the remaining requested service. Lastly the Study estimated the cost of the proposed reinforcements and the earliest estimated in-service date. This report summarizes the results of the technical studies, the estimated costs, and the earliest in-service dates. 3/12/09 ​
​4/25/2008 BPA-TS TPP-2008-041 Powerex SIS (AREF 71926625+) 
Powerex submitted long-term firm point-to-point (PTP) Transmission Service Requests (TSR’s) (AREF numbers 71926625 and 71926626) to BPA Transmission Services (BPA-TS) through the Open Access Transmission Tariff (OATT). The TSR’s totaled 100 MW with a point-of-receipt (POR) at Rock Creek 230 kV and a point-of-delivery (POD) at the BC-US Border (East). BPA-TS’ ATC analysis determined that there was insufficient long-term firm ATC to grant the requested service.  The SIS identified Cross Cascades South and potentially the Northern Intertie if BPA-TS is unable to schedule on the east, as the constraining paths.  This SIS identified the potential transmission system expansion to mitigate the system constraints and grant the requested service.  This SIS is available upon request subject to a non-disclosure agreement.
​4/25/2008 BPA-TS TPP-2008-040 Powerex SIS (AREF 71926623+)
Powerex submitted long-term firm point-to-point (PTP) Transmission Service Requests (TSR’s) (AREF numbers 71926623 and 71926624) to BPA Transmission Services (BPA-TS) through the Open Access Transmission Tariff (OATT). The TSR’s totaled 100 MW with a point-of-receipt (POR) at McNary 230 kV and a point-of-delivery (POD) at the BC-US Border (West). BPA-TS’ ATC analysis determined that there was insufficient long-term firm ATC to grant the requested service.  The SIS identified Cross Cascades North, Cross Cascades South, West of McNary, West of Slatt, and the Northern Intertie as the constraining paths.  This SIS identified the potential transmission system expansion to mitigate the system constraints and grant the requested service.  This SIS is available upon request subject to a non-disclosure agreement. 
4/25/2008​ BPA-TS TPP-2008-039 Powerex SIS (AREF 71926619+)
Powerex submitted long-term firm point-to-point (PTP) Transmission Service Requests (TSR’s) (AREF numbers 71926619, 71926620, 71926621, and 71926622) to BPA Transmission Services (BPA-TS) through the Open Access Transmission Tariff (OATT). The TSR’s totaled 200 MW with a point-of-receipt (POR) at Rock Creek 230 kV and a point-of-delivery (POD) at the BC-US Border (West). BPA-TS’ ATC analysis determined that there was insufficient long-term firm ATC to grant the requested service.  The SIS identified Cross Cascades North, Cross Cascades South, and the Northern Intertie as the constraining paths.  This SIS identified the potential transmission system expansion to mitigate the system constraints and grant the requested service.  This SIS is available upon request subject to a non-disclosure agreement.​
4/25/2008​ BPA-TS TPP-2008-037 PAC Rock Creek- MidC SIS (71872570) 
PacifiCorp submitted a long-term firm point-to-point (PTP) Transmission Service Request (TSR) (AREF number 71872570) to BPA Transmission Services (BPA-TS) through the Open Access Transmission Tariff (OATT). The TSR was for 56 MW with a point-of-receipt (POR) at Rock Creek 230 kV and a point-of-delivery (POD) at MidC Remote. BPA-TS’ ATC analysis determined that there was insufficient long-term firm ATC to grant the requested service.  The SIS identified Cross Cascades North and Cross Cascades South as the constraining paths.  This SIS identified the potential transmission system expansion to mitigate the system constraints and grant the requested service.  This SIS is available upon request subject to a non-disclosure agreement.
4/25/2008 ​ BPA-TS TPP-2008-036 Finley Bioenergy SIS (71915090)
Finley Bioenergy submitted a long-term firm point-to-point (PTP) Transmission Service Request (TSR) (AREF number 71915090) to BPA Transmission Services (BPA-TS) through the Open Access Transmission Tariff (OATT). The TSR was for 1 MW with a point-of-receipt (POR) at Boardman 115 kV and a point-of-delivery (POD) at Troutdale 230 kV. BPA-TS’ ATC analysis determined that there was insufficient long-term firm ATC to grant the requested service. The SIS concluded that while the ATC analysis identified non de minimis impacts across the Cross Cascades North, Cross Cascades South, West of McNary and West of Slatt flowgates, these impacts were too small to cause any adverse reliability concerns requiring potential system expansion across the monitored flowgates.  Also, there were no sub-grid impacts associated with this request and no further analysis was necessary to grant the requested service.  This SIS is available upon request subject to a non-disclosure agreement.
4/25/2008 ​ BPA-TS TPP-2008-035 BPA-TS SIS (1472913)
Bonneville Power Administration – Power Services submitted a long-term firm point-to-point (PTP) Transmission Service Requests (TSR) (AREF number 1472913) to BPA Transmission Services (BPA-TS) through the Open Access Transmission Tariff (OATT). The TSR was for 2 MW with a point-of-receipt (POR) at McNary 230 kV and a point-of-delivery (POD) at John Day 500 kV. BPA-TS’ ATC analysis determined that there was insufficient long-term firm ATC to grant the requested service. The SIS concluded that while the ATC analysis identified non de minimis impacts across the West of Slatt flowgate, these impacts were too small to cause any adverse reliability concerns requiring potential system expansion across the monitored flowgate.  Also, there were no sub-grid impacts associated with this request and no further analysis was necessary to grant the requested service.  This SIS is available upon request subject to a non-disclosure agreement.  ​
4/25/2008 ​ BPA-TS TPP-2008-034 PAC SIS (71642789)
PacifiCorp submitted a long-term firm point-to-point (PTP) Transmission Service Request (TSR) (AREF number 71642789) to BPA Transmission Services (BPA-TS) through the Open Access Transmission Tariff (OATT). The TSR was for 1 MW with a point-of-receipt (POR) at Vantage 230 kV MidC Remote and a point-of-delivery (POD) at Rock Creek 230 kV. BPA-TS’ ATC analysis determined that there was insufficient long-term firm ATC to grant the requested service. The SIS concluded that while the ATC analysis identified non de minimis impacts across the Cross Cascades North, Cross Cascades South, and North of John Day flowgates, these impacts were too small to cause any adverse reliability concerns requiring potential system expansion across the monitored flowgates.  Also, there were no sub-grid impacts associated with this request and no further analysis was necessary to grant the requested service. This SIS is available upon request subject to a non-disclosure agreement.​
4/25/2008​ BPA-TS TPP-2008-024 PPM Slatt-John Day, Slatt-Big Eddy SIS (AREF 7149295+)
PPM Energy submitted ten long-term firm point-to-point (PTP) Transmission Service Requests (TSR’s) to BPA Transmission Services (BPA-TS) through the Open Access Transmission Tariff (OATT). The TSR’s totaled 500 MW with a point-of-receipt (POR) at Slatt 500 kV and points-of-delivery (POD) at John Day 500 (250 MW) and Big Eddy (250 MW). BPA-TS’ ATC analysis determined that there was insufficient long-term firm ATC to grant the requested service.  The SIS identified West of Slatt as the constraining path.  This SIS identified the potential transmission system expansion to mitigate the system constraints and grant the requested service.  This SIS is available upon request subject to a non-disclosure agreement.​
​4/25/2008
BPA-TS TPP-2008-023 PSEI SIS (AREF 71487657+)
Puget Sound Energy, Inc. submitted long-term firm point-to-point (PTP) Transmission Service Requests (TSR’s) (AREF numbers 71487657 and 71487663) to BPA Transmission Services (BPA-TS) through the Open Access Transmission Tariff (OATT). The TSR’s totaled 206 MW with a points-of-receipt (POR) at Harvalum 230 kV (56 MW) and Midway 230 kV (150 MW) and a point-of-delivery (POD) at PSEI Central Contiguous. BPA-TS’ ATC analysis determined that there was insufficient long-term firm ATC to grant the requested service.  The SIS identified Cross Cascades North and North of John Day as the constraining paths.  This SIS identified the potential transmission system expansion to mitigate the system constraints and grant the requested service.  This SIS is available upon request subject to a non-disclosure agreement.​
​4/25/2008 BPA-TS TPP-2008-022 PacifiCorp SIS (AREF 71469578)
PacifiCorp submitted long-term firm point-to-point (PTP) Transmission Service Requests (TSR) (AREF number 71469578) to BPA Transmission Services (BPA-TS) through the Open Access Transmission Tariff (OATT). The TSR was for 99 MW with a point-of-receipt (POR) at Rock Creek 230 kV and a point-of-delivery (POD) at Troutdale 230 kV. BPA-TS’ ATC analysis determined that there was insufficient long-term firm ATC to grant the requested service.  The SIS identified Cross Cascades North as the constraining path.  This SIS identified the potential transmission system expansion to mitigate the system constraints and grant the requested service.  This SIS is available upon request subject to a non-disclosure agreement.​
4/25/2008 ​ BPA-TS TPP-2008-021 Powerex SIS (AREF 71444926+)
Powerex submitted long-term firm point-to-point (PTP) Transmission Service Requests (TSR’s) (AREF numbers 71444926 and 71444928) to BPA Transmission Services (BPA-TS) through the Open Access Transmission Tariff (OATT). The TSR’s total 100 MW with a point-of-receipt (POR) at Hot Springs 230 kV and a point-of-delivery (POD) at BC-US Border (West). BPA-TS’ ATC analysis determined that there was insufficient long-term firm ATC to grant the requested service.  The SIS identified Cross Cascades North, as well as the Northern Intertie as the constraining paths.  This SIS identified the potential transmission system expansion to mitigate the system constraints and grant the requested service.  This SIS is available upon request subject to a non-disclosure agreement.​
​4/25/2008 BPA-TS TPP-2008-020 PacifiCorp SIS (AREF 1473081)
PacifiCorp submitted a long-term firm point-to-point (PTP) Transmission Service Request (TSR) (AREF number 1473081) to BPA Transmission Services (BPA-TS) through the Open Access Transmission Tariff (OATT). The TSR was for 13 MW with a point-of-receipt (POR) at Dalreed 230 kV and a point-of-delivery (POD) at Troutdale 230 kV. BPA-TS’ ATC analysis determined that there was insufficient long-term firm ATC to grant the requested service.  The SIS identified Cross Cascades North, West of McNary and West of Slatt, as well as the McNary-Santiam 230 kV line as the constraining paths.  This SIS identified the potential transmission system expansion to mitigate the system constraints and grant the requested service.  This SIS is available upon request subject to a non-disclosure agreement.​
​4/25/2008 BPA-TS TPP-2008-019 PSEI SIS (AREF 71503549)
Puget Sound Energy, Inc. submitted a long-term firm point-to-point (PTP) Transmission Service Request (TSR) (AREF number 71503549) to BPA Transmission Services (BPA-TS) through the Open Access Transmission Tariff (OATT). The TSR was for 7 MW with a point-of-receipt (POR) at Tucannon River 115 kV and a point-of-delivery (POD) at Covington 230 kV. BPA-TS’ ATC analysis determined that there was insufficient long-term firm ATC to grant the requested service.  The SIS identified Cross Cascades North, North of John Day, West of McNary and West of Slatt as the constraining paths.  This SIS identified the potential transmission system expansion to mitigate the system constraints and grant the requested service.  This SIS is available upon request subject to a non-disclosure agreement.​
​4/25/2008 BPA-TS TPP-2008-018 PacifiCorp SIS (AREF 71507893+)
PacifiCorp submitted long-term firm point-to-point (PTP) Transmission Service Requests (TSR’s) (AREF numbers 71507893 and 71507900) to BPA Transmission Services (BPA-TS) through the Open Access Transmission Tariff (OATT). The TSR’s total 50 MW with a point-of-receipt (POR) at Willow Creek Wind on the Boardman-Alkali 115 kV line and a point-of-delivery (POD) at McNary 230 kV (25MW) and Vantage 230 kV MIDCR (25 MW). BPA-TS’ ATC analysis determined that there was insufficient long-term firm ATC to grant the requested service.  The SIS identified Cross Cascades North, West of McNary and West of Slatt as the constraining paths.  This SIS identified the potential transmission system expansion to mitigate the system constraints and grant the requested service.  This SIS is available upon request subject to a non-disclosure agreement.​
​4/25/2008
BPA-TS TPP-2008-017 Mason PUD SIS (AREF 1472570)
Mason County PUD #3 submitted a network transmission (NT) Transmission Service Request (TSR) (AREF number 1472570) to BPA Transmission Services (BPA-TS) through the Open Access Transmission Tariff (OATT). The TSR was for 1 MW with a point-of-receipt (POR) at Nine Canyon Wind and a point-of-delivery (POD) at Mason PUD #3. BPA-TS’ ATC analysis determined that there was insufficient long-term firm ATC to grant the requested service. The SIS concluded that while the ATC analysis identified non de minimis impacts across the West of Slatt and West of McNary flowgates, these impacts were too small to cause any adverse reliability concerns requiring potential system expansion across the monitored flowgates.  Also, there were no sub-grid impacts associated with this request and no further analysis was necessary to grant the requested service.  This SIS is available upon request subject to a non-disclosure agreement
​4/25/2008 BPA-TS TPP-2008-016 Puget Sound Energy Saddleback SIS (AREF 71618267+)
Puget Sound Energy, Inc. submitted long-term firm point-to-point (PTP) Transmission Service Requests (TSR’s) (AREF numbers 71618267, 71618279, 71618281, and 71618283) to BPA Transmission Services (BPA-TS) through the Open Access Transmission Tariff (OATT). The TSR’s totaled 75 MW with a point-of-receipt (POR) at Saddleback 230 kV and a point-of-delivery (POD) at PSEI Central Contiguous. BPA-TS’ ATC analysis determined that there was insufficient long-term firm ATC to grant the requested service.  The SIS identified Cross Cascades North and Cross Cascades South as the constraining paths.  This SIS identified the potential transmission system expansion to mitigate the system constraints and grant the requested service.  This SIS is available upon request subject to a non-disclosure agreement ​
​4/25/2008
BPA-TS TPP-2008-014 Horizon Sagebrush SIS (LTRQ 1139-1143)
This is a revised System Impact Study (SIS) report that updates an earlier SIS.  Horizon Wind Energy, LLC submitted long-term firm point-to-point (PTP) Transmission Service Requests (TSR’s) (Long Term Request Queue numbers 1139-1143) to BPA Transmission Services (BPA-TS) through the Open Access Transmission Tariff (OATT). The TSR’s totaled 195 MW with a point-of-receipt (POR) at Kittitas Wind 230-kV and a point-of-delivery (POD) at NW Hub. BPA-TS’ ATC analysis determined that there was insufficient long-term firm ATC to grant the requested service.  The SIS identified North of John Day as the constraining path.  This SIS identified the potential transmission system expansion to mitigate the system constraints and grant the requested service.  This SIS is available upon request subject to a non-disclosure agreement.​